LTCCS-01A
THE TYPE LTC TEMPERATURE CONTROL VALVE IS A DOUBLE-PORT VALVE WITH A RANGE OF 0 TO -40°F (-17 TO -40°C) FOR LOW TEMPERATURE CUT-OFF. AS IT IS SUBJECT TO AMBIENT TEMPERATURE UNDER NORMAL CONDITIONS, IT WILL NORMALLY BE IN A WIDE-OPEN POSITION. A COPPER WELL IS RECOMMENDED FOR EACH INSTALLATION, WHICH ALLOWS THE REMOVAL OF THE CAPILLARY BULB WITHOUT DEPRESSURIZING THE SYSTEM. NOTE: VALVE SEAT CLOSURE MAY TAKE SEVERAL SECONDS UNDER NORMAL OPERATING CONDITIONS. IN ADDITION, TYPE LTC FAILS IN THE CLOSED POSITION. TYPE LTC IS NOT INTENDED TO BE BUBBLE TIGHT ON CLOSING. IT IS ONLY MEANT TO DRASTICALLY REDUCE FLOW ON SENSING TEMPERATURE BASED ON SET.